Electric Boiler Features
● The electric boiler is produced in accordance with the national "Steam Boiler Safety and Technical Supervision Regulations" and relevant professional standards and regulations for boiler manufacturing, and at the same time absorbs the excellent performance of similar products at home and abroad.
● The electric boiler is equipped with multiple automatic protection devices such as pressure gauge, safety valve, automatic pressure controller, automatic water supply device, and low water level automatic stop heating device.
● The electric boiler has a complete automatic control system. As long as you turn on the input power, the boiler will immediately enter the fully automatic operation state, which greatly facilitates your use.
Part of the furnace body is made of Q235 steel, please refer to the product quality certificate for specific data.
● The electric boiler is small in size. It's light in weight and easy to move.
Electric boiler Operation Procedure
Choose the right power supply:
Electric boiler Precautions
• The factory original parts have been debugged, and must not be adjusted arbitrarily, and other large-value safety valves and other parts must be replaced.
• During the working process, the water tank of boiler must not be short of water, otherwise water pump idle, and be easily damaged. If you add water when the water tank is lack of water, there is a phenomenon that the water pump can’t supply the water for the boiler. if the water pump cannot supply the water, it means that there is air in the water pump after the water is cut off, you can unscrew the exhaust bolt of the water pump, and add water typically after discharging the air in the water pump.
• After one month of use, the electric heating heat pipe should be disassembled, and the furnace should be cleaned to remove scale (depending on the local water quality), so as to ensure the steam production, the purity of the steam, and prolong the service life.
• Pressure controllers and pressure gauges should be inspected and calibrated by the local standard measurement department every year.
• When repairing and replacing parts, it is necessary to turn off the power and vent the remaining steam, and never work with steam.
• When discharging sewage, connect the outlet of the sewage pipe to a safe place to avoid scalding personnel.
Electric boiler Troubleshooting
Trouble | Remedy |
---|---|
Power on does not work or heating very slowly |
Check whether the power supply is out of phase, Whether the Zero line is connected, Is the voltage too low |
The phenomenon of jumping back and forth of the AC contactor during work |
Check if the power supply voltage is too low; Check whether the probe wire is in good contact; Is the ground wire on the body loose? Whether the wiring is correct |
When the air pressure rises to the set value or falls to the set value, the heating AC contactor jumps back and forth | Unstable contact of pressure controller |
Turn on the boiler for the first time or turn it on again after it is not in use, and find that the green light is on, but the water pump does not work | If the water pump is stuck, stop it immediately, open the rear end cover of the water pump, and rotate the shaft. |
The water pump keeps adding water |
Check whether the probe circuit screw is in good contact; Clean the dirt on the probe or replace the probe |
If the work was normal yesterday, and the water in the furnace is found to be full when the machine is turned on today | It may be that the residual steam was not discharged when the machine was shut down yesterday. After the air pressure cooled down, a negative pressure was formed in the furnace and the water in the water tank was sucked into the furnace by itself. At this time, just open the drain valve and let off the excess water to restart the machine. |